CS2 Series Motor Protection Circuit Breaker
Katrangan
Nilai listrik: AC690V, 32A, 80A;
Standar: IEC / EN 60947-2, IEC60947-4-1
Jeneng Tipe
Kondisi Operasi
3.1 Suhu: -5 ℃ ~ + 40 ℃, suhu rata-rata ing 24 jam ora ngluwihi +35 ℃
3.2 Dhuwur: ora ngluwihi 2000m
3.3 Kondisi Udara:
Ing situs sing dipasang, kelembapan relatif ora ngluwihi 50% ing suhu maksimal +40 ℃, luwih dhuwur
Kelembapan relatif diijini ing suhu sing luwih murah, contone, RH bisa 90% ing +20 ℃
3.4 Kelas polusi: Kelas Ⅲ
3.5 Release kelas: 10A(CS2-32) 10A(CS2-80)
3.6 Sistem operasional sing dirating: Sistem operasional sing terus-terusan
3.7 Kondisi pemasangan:
Ing karep antarane bidang soyo tambah lan bidang vertikal ora ngluwihi 5 ° Prodhuk bakal diinstal lan dilakokno ing panggonan tanpa goyang ketok, Impact lan geter.
Spesifikasi Teknis
Seri No. | Multiple setelan saiki | Status wiwitan | Wektu | asil samesthine | Suhu sekitar | |
1 | 1.05 | Status dingin | t≥2h | Non-tripping | +20 ℃ ± 2 ℃ | |
2 | 1.20 | Status panas (sawise tes.1) | t;2h | Kesandung | +20 ℃ ± 2 ℃ | |
3 | 1.50 | Status panas (sawise tes.1) | Kelas tripping | 10A t<2min | Kesandung | +20 ℃ ± 2 ℃ |
10 jam < 4 min | ||||||
4 | 7.20 | Status dingin | Kelas tripping | 10A 2s <t≤10s | Kesandung | +20 ℃ ± 2 ℃ |
Proteksi gagal fase
Seri No. | Multiple setelan saiki | Status wiwitan | Wektu | asil samesthine | Suhu sekitar | |
2 phase wae | Fase liyane | |||||
1 | 1.0 | 0.9 | Status dingin | t≥2h | Non-tripping | +20 ℃ ± 2 ℃ |
2 | 1.15 | 0 | Status panas (sawise tes.1) | t <2h | Kesandung | +20 ℃ ± 2 ℃ |
Sifat kompensasi suhu
Seri No. | Multiple setelan saiki | Status wiwitan | Wektu | asil samesthine | Suhu sekitar |
1 | 1.0 | Status dingin | t≥2h | Non-tripping | +40 ℃ ± 2 ℃ |
2 | 1.2 | Status panas (sawise tes.1) | t;2h | Kesandung | +40 ℃ ± 2 ℃ |
3 | 1.05 | Status dingin | t≥2h | Non-tripping | -5 ℃ ± 2 ℃ |
4 | 1.3 | Status panas (sawise tes.3) | t;2h | Kesandung | -5 ℃ ± 2 ℃ |
Model relay kakehan | Kode | Rated saiki (A) | Kapasitas putus hubung singkat utama Icu (kA) | Kapasitas putus hubung singkat layanan dinilai Ics (kA) | Daya dirating standar saka motor telung fase (kW) | ||||||
230/240 V | 400/415V | 660/690V | 230/240 V | 400/415V | 660/690V | 230/240 V | 400/415V | 660/690V | |||
CS2-32 | 3201 | 0.1~0.16 | 100 | 100 | 100 | 100 | 100 | 100 | - | - | - |
3202 | 0.16~0.25 | 100 | 100 | 100 | 100 | 100 | 100 | - | - | - | |
3203 | 0.25~0.4 | 100 | 100 | 100 | 100 | 100 | 100 | - | - | - | |
3204 | 0.4~0.63 | 100 | 100 | 100 | 100 | 100 | 100 | - | - | 0.37 | |
3205 | 0.63~1 | 100 | 100 | 100 | 100 | 100 | 100 | - | - | 0.55 | |
3206 | 1~1.6 | 100 | 100 | 100 | 100 | 100 | 100 | - | - | 1.1 | |
3207 | 1.6~2.5 | 100 | 100 | 3 | 100 | 100 | 2.25 | 0.37 | 0.75 | 1.5 | |
3208 | 2.5~4 | 100 | 100 | 3 | 100 | 100 | 2.25 | 0.75 | 1.5 | 3 | |
3210 | 4~6.3 | 100 | 100 | 3 | 100 | 100 | 2.25 | 1.1 | 2.2 | 4 | |
3214 | 6~10 | 100 | 100 | 3 | 100 | 100 | 2.25 | 2.2 | 4 | 7.5 | |
3216 | 9~14 | 100 | 15 | 3 | 100 | 7.5 | 2.25 | 3 | 5.5 | 9 | |
3220 | 13~18 | 100 | 15 | 3 | 100 | 7.5 | 2.25 | 4 | 9 | 11 | |
3221 | 17~23 | 50 | 15 | 3 | 50 | 6 | 2.25 | 5.5 | 11 | 15 | |
3222 | 20~25 | 50 | 15 | 3 | 50 | 6 | 2.25 | 5.5 | 11 | 18.5 | |
3232 | 24~32 | 50 | 15 | 3 | 50 | 6 | 2.25 | 7.5 | 12.5 | 22 | |
CS2-80 | 8025 | 16~25 | - | 15 | - | - | 7.5 | - | 5.5 | 11 | - |
8040 | 25~40 | - | 15 | - | - | 7.5 | - | 11 | 22 | - | |
8063 | 40~63 | - | 15 | - | - | 7.5 | - | 15 | 33 | - | |
8080 | 56~80 | - | 15 | - | - | 7.5 | - | 22 | 45 | - |